Power Correction in Three phase

Power factor is the ratio between the Power (Watt) and the Apparent Power measured in VA(voltage-ampere)  drawn by an electrical load . It is written as PF= P/S.

Using the Power triangle:

images

P= VpIpcosθ

S= VpIp

Q=Ssinθ

S= VpIp*   w/ angle

We can sum up all the Power and  Apparent Power (S).

P = P1 + P2 + P3

S= S1 + S2 + S3

EXAMPLE

Untitled111

LINE VOLTAGE = 34.5     60Hz             Find C when the power factor is 0.94                                                                                                                                                                                                    leading

Solve first the P, S and Q using the 0.78 pf lagging.

Using the power triangle:

pf= arcos(0.78) = 38.74

The given is the Apparent Power equal to 24 MVA, we only need to solve the P and Q  to complete the triangle.

P = Scos38.74

P = 24cos38.74

P =  18.72 MV

Q= Ssin38.74

Q = 24sin38.74

Q = 15.01 MVAR

These values is for the old.

Untitled111

FOR THE NEW ONE

Using the 0.94 pf leading and the P= 18.72   ( note that the power will just the same to the old one)

θ= arcos(0.94)

θ= 19.94

solve the Q;

using the trigonometric function

Q=Ptanθ

Q= 18.72tan(19.94)

Q= 6.79MVAR

we can disregard the S, since we only need the  Q.

the power triangle for the New one is:

Untitled111

Since the Q in the new is in below, the sign is  negative

Qc= Qnew – Qold

Qc= -6.79 -15.01

Qc = -21.79

Solving for the Capacitor

C= Q/2πf V^2rms

C= -21.79×10^6/ 2π(60) (34.5×10^3)^2

C= + 48 microFarad   (disregard the sign)

 